Friday, January 17, 2014

Is Your Dust Collector NFPA Compliant?

Blast Plate & Vertical Plenum

Combustible dust explosions are a risk in many areas of a plant, but one of the most common locations is the dust collection system. How do you know if your dust collection system complies? What do you do if it doesn’t? Are your employees at risk?


The following is a list of components that can be installed on your dust collector to comply with new NFPA Fire and Explosion Standards 484-2012 and 654-2013 for Combustible Dusts to ensure a safe workplace for your employees.


Blast Plate
A Blast Plate is a deflector mounted directly in front the explosion relief area. The deflector is designed to restrict the flame length ejected from the collector in the event of an explosion. For vessels that are not greater than 706 cubic feet, the deflector is designed to reduce the axial (front-centerline) safe distance by 50 percent.

Vertical Plenum
A plenum that is bolted to the dirty air section of the collector. The explosion vent is mounted to the top of the plenum which effectively transitions the pressure and flame fronts from a horizontal to a vertical configuration. A vertical configuration makes it possible to explosion vent through a roof and/or direct the pressure and flame fronts to a safe location as outlined in NFPA standards. In most cases, ducting and weather hoods are required to be compliant with NFPA standards to protect the explosion vents from the elements and other debris. Access panels are provided on the ducting so that easy inspection and/or replacement of the explosion vent is made possible without removing the ducting and weather hood.

An NFPA compliant dust collector

Inlet Protection


Fast Acting Valve
Designed to close within milliseconds of detecting an explosion, the fast acting valve installs in either inlet and/or outlet ducting. The fast acting valve creates a mechanical barrier within the ducting which effectively isolates pressure and flame fronts (from either direction) from being able to propagate further through the process.

Inlet/Outlet Chemical Isolation
Designed to react within milliseconds of detecting an explosion, a chemical isolation systems can be installed in either inlet and/or outlet ducting. The chemical isolation system creates a chemical barrier that suppresses the explosion within the ducting and reduces the propagation of flame through the ducting and minimizes pressure increases within connected process equipment.

Backdraft Damper
The mechanical backdraft damper was designed to be installed in the inlet ducting. The damper utilizes a mechanical barrier that is held open by the process air and is slammed shut by the pressure forces of the explosion. When closed, the mechanical barrier isolates pressure and flame fronts from being able to propagate further up the process stream.

Detect and Suppress
These systems protect the dust collector from ignition sources such as sparks or embers.  It detects them and activates a suppression system that extinguishes them before they reach the collector.

Outlet Protection


Integrated Safety Monitoring Filter
The iSMF has been proven to isolate the downstream equipment from the progression of a flame front during an explosion. A dust collector with an integrated Safety Monitoring Filter allows you to recirculate exhaust air back into the work space when your dust is explosive, preventing the transmission of explosive dust (fuel) from the collector.

High Speed Abort Gates
High speed abort gates are designed to be installed in the outlet ducting of the dust collection system. The devices are designed to divert process air and/or smoke to a safe location outside when a possible ignition source is detected entering the dust collection system or when a fire is detected. It’s primary purpose is to protect the inside of the building from burning debris, embers or smoke.

Explosion Venting


Explosion Vent
Designed to be the “weak” link of the vessel, explosion vents open when predetermined pressures are reached inside the dust collector allowing the overpressure and flame fronts to exit to a safe area. Explosion vents minimize damage to the dust collector caused by overpressure created by a deflagration.

Flameless Vent
Designed to install over a standard explosion vent, a flameless vent extinguishes the flame front exiting the vented area not allowing it to exit the device. This allows conventional venting to be accomplished indoors where it could otherwise endanger personnel and/or ignite secondary explosions.

Chemical Suppression
Designed to react within milliseconds of detecting an explosion, a chemical suppression system is installed in the collectors dirty air section, being it in the filter housing or the hopper. The chemical suppression system prevents expanding a deflagration by releasing a chemical agent.


For more information about NFPA compliance, read our white paper on the Camfil APC website.

If you think that the Farr Gold Series would be a good choice for NFPA compliance, you can read more information about it on our products page.